Model | VX-3004F |
Power supply | 31 V DC (operating range: 20 - 40 V DC) |
Frequency response | 40 Hz - 20 kHz (±1 dB) |
Distortion | < 1 % |
Energy consumption | max. 85 W a 31 VDC |
S/N ratio | 60 dB (or more) |
Control input | 16 (by contact) + 2 (by change of polarity of 24 VCC) |
Control output | Open collector: 8 + 3 (CPU OFF), Relay (125 VDC, 5 A): 8 |
Input / Output | Speaker output: 4 AB areas. Audio input: 4 (Line: -20 dBV / Microphone -60 dBV, phantom power supply selectable) |
Indicator | Power on, running, CPU off, LAN status, RM status State failures of emergency: general, network, emergency microphone, fuse, power supply, CPU, areas Amplifier status: signal, peak, operation, power |
Connection | RJ45: control inputs x 2, control outputs (open collector) x 2, DS link x 1, remote microphones x 2, LAN x 2, analog link x 2. Removable screw terminals: control outputs (relay), area outputs, standby amplifier bus, extension links, power input, audio inputs |
Operating Humidity | 90% or less |
Operating temperature | -5°C up to +45°C |
Finished | Steel plate, surface treated, 30% brightness, painted, black |
Dimensions | 482 x 132.6 x 345 mm (D x H x W) |
Weight | 7,6 kg |
Accessory (included) | CD (PC configuration software) x 1, removable terminal connector (2 pins) x 2, removable terminal connector (4 pins) x 1, removable terminal connector (6 pins) x 2, removable terminal connector (12 pins) x 2, removable terminal connector (17 pins) x 1, ferrite cable clamp x 2 |