Primary power supply | Switching source 110-252V AC 50-60 Hz 55W max. |
Backup power supply | 2 batteries 12VDC (up to 5 Ah). Ensures minimum 72 hours duration. |
Number of extension lines | 2 cross-connected lines |
Number of detection zones | 1 conventional zone, up to 30 detectors per zone. |
Push-button inputs | Manual, Hold, Select mode, ON/OFF extinguishing and low pressure. |
Siren outputs | 2 siren outputs 24VDC. Independent and monitored open collector outputs |
Relay outputs | 4 Relay outputs: [VAR%] Alarm output, 1 Fault output and 1 configurable relay outputs. All support 30VDC 3A max. |
Open collector outputs | 4 outputs |
End of line resistance | Areas fully monitored by end-of-line resistance (4.7K) |
Auxiliary Output Voltage | 24VDC. Protected by resettable electronic fuse 1A |
Protection Index | IP30 |
Temperature | -5ºC~+40ºC |
Material and colour | ABS, colour: White |
Dimensions | 310 x 240 x 80 mm |
Weight | 1,3Kg |
Recommended cable | Fire cable with a minimum section of 1.0mm (18AWG). |