Reference | EK-WL8-OH |
Operating frequency range | 866 - 869,85 MHz |
Communication range with a transceiver or expander | 1200 m |
Type of modulation
| GFSK |
Operating frequency channels | 6 |
Max. radiated power | ≤ 25 mW |
Operating temperature range | - 10 °C to + 55 °C |
IP Rating
| IP23 |
Operating modes
| Only smoke Heat only A1R Combined smoke and heat A1R |
Max. tolerated humidity (no condensation) | 95% RH |
Dimensions (mm) | 160 / Ø 111 x H 57 |
Power supply
(Dual lithium batteries of 3 V) | 1 x primary cell (CR123A) 1 x secondary cell (CR2032) 1,2 Ahr 0,24 Ahr Up to 10 years main battery* 3 months secondary battery life |
Standards and Certificates | BS EN 54-5 Hot spot detectors BS EN 54-7 Smoke Detectors BS EN54-25: Components using radio links BS EN54-29: multisensor fire detectors CEA4021 |