CHQ-DRC2(SCI)

  • Dual-relay analog module with SCI
  • Powered from the loop
  • Single loop steering
  • 2 relay outputs
  • Monitored auxiliary input
  • Description
  • Specifications
  • Contents
  • Downloads

CHQ-DRC2(SCI) is a relay controller module designed to provide 2 general purpose relay outputs, each of which can be controlled separately to manage devices such as gates or to control the shutdown of plant and equipment.

The supervised input can be used for fault monitoring or as a general purpose input.

Available in DIN-mounted version, both models have integrated short-circuit isolator.

A subsequent box (CHQ-BACKBOX) is also available which, when used in conjunction with the CHQ-DRC2(SCI), increases the IP rating to IP65.

  • HOCHIKI
  • Analog module of 2 relays with SCI
  • Loop-powered
  • Single loop steering
  • Provides 2 independently controlled changeover relays
ReferenceCHQ-DRC2(SCI)
Operating voltage 17 - 41 VCC
Low power mode (0,75 s) 170 μA
Standby current (typical)300 μA
Power consumption 22 mA ± 20 % (polling)
Short circuit current 8 mA
Maximum short circuit current1 A
Relay contact classification 30 VCC max., 1 A (resistive load)
EOL input resistance 10 kΩ, ±5%, 0,25 W
Entry threshold level ON=470 Ω, Cortocircuito <50 Ω, Circuito abierto >100 KΩ
Operating temperature range -10°C a + 50°C
Storage temperature range -30°C a + 60°C
Maximum humidity 95%RH - No condensation (at 40°C))
Weight (g) Dimensions (mm)Module cabinet 343 (add 235 to the weight when using
CHQ-BACK BOX) L157 x W127 x D35 (Module y
lid) D79 (Module, Lid + CHQ-BACKBOX)
DIN box 124 L119 x H108 x H24
Color and materialCHQ module and CHQ-BACKBOX ABS white, DIN module ABS green, ABS module cover ABS black semi-opaque as standard
(white version - CHQ-LID(WHT) also available)
  • Analog module of 2 relays with SCI