  • Analog module with 4 inputs and 4 outputs
  • Powered from the loop
  • Single loop steering
  • Supervised independent inputs
  • normally open or normally closed contacts
  • Incorporates integral ICS
  • Description
  • Specifications
  • Contents
  • Downloads

CHQ-PCM(SCI) is a loop-powered input/output module with 4 independent relay outputs and 4 supervised inputs.

Outputs are provided with voltage-free N/O and N/C contacts and can be driven separately under panel control, to be used for control of devices such as gates, or shutdown of plant and equipment.

The 4 inputs allow local fire and fault monitoring, monitoring open circuit and short circuit, and if required, can be enabled or disabled in pairs using a two-way DIL switch.

When using heavy cables, we recommend the use of the SMB-1 modular housing in conjunction with SMB-ADAPTOR, a back box (CHQ-BACKBOX) is available which, when used in conjunction with the CHQ-PCM(SCI), increases the IP rating to IP65.

Also available in DIN-mountable housing: CHQ-PCM/DIN(SCI)

Note: The status of the relay contacts will be indeterminate until the unit is turned on.

  • HOCHIKI
  • Analog addressable control module with 4 inputs and 4 outputs
  • Loop-powered
  • Supervised auxiliary input
ReferenceCHQ-PCM(SCI)
Operating voltage 17 - 41 VCC
Method of transmission Digital communication via ESP
Standby current (typical) 330 μA
Current consumption (during polling) 22 mA ± 20 %
Relay contact classification 30 VCC max., 1 A (resistive load)
Input EOL resistance 10 K Ω, ±5 %, 0,25 W
Entry threshold level ON=470 Ω, circuito corto <50 Ω, circuito abierto >100 KΩ
Maximum rated current1 A (switch closed)
Leakage current3 mA (open switch)
Weights (g) / Dimensions (mm)CHQ-PCM (SCI) 322 (567 with lid and back box) L 157 x W 127 x D 35 (with lid)(with lid and back box) D 79
Pressure range atmospheric - No restrictions specified