CHQ-SOM

Shipping in
48h
  • 1 output module
  • Powered from the loop
  • Single loop steering
  • Includes a single supervised output
  • Description
  • Specifications
  • Contents
  • Downloads

CHQ-SOM has been designed to allow the connection of 1 relay output to the ESP loop.


Incorporates 1 voltage-free relay contact that can be used as N/O or N/C, the contact has a rated capacity of 30 VDC (maximum), 1 A (resistive load).


It has 3 color-coded connection wires, as well as a wiring terminal block for loop connection.


To maintain LPCB approval, the device must be mounted in an SMB-1 housing (or an equivalent housing made of polycarbonate or similar material that is impact resistant according to EN54-18:2005 Clause 5.9) together with SMB-ADAPTOR, using two screws or two nuts M3.


NOTE: The status of the relay contacts will be indeterminate until the unit is powered on, if the PCB is removed from the protective outer casing, the EN54 certification is cancelled.


  • HOCHIKI
  • 1 output module
  • Loop-powered
ReferenceCHQ-SOM
Operating voltage 17 - 30 VCC
Standby/alarm current 150 μA (@ 41 V) (typical)
Starting classifications: maximum voltage30 VCC
Starting classifications: peak current 1 A (resistive load)
Operating/storage temperature range - 10 °C at + 50 °C / - 30 °C at + 60 °C
Maximum humidity 95% RH - Non-condensing (at 40 °C)
Color / Material of the box Ivory / ACS
Weight (g) / Dimensions (mm) 25 / L 65 x A 42 x Bottom 15