Brand | Kilsen |
Display | 240 x 64 white backlit LCD screen. |
LED indicators | Main: Power, Test, Disabled, Fault, Alarm Other: Different system failures |
Number of zones | 512 |
Number of loops | 1 |
Loop devices | 250 |
Loop load capacity | 250mA |
Recommended cable length and type | Recommended twisted pair of 2 cores of 1,5 mm² 56ohm / 1μF max. 4 km |
Outputs on board | Programmable supervised: 2, 750mA / nominal 19.5-28VDC (24VDC ) Fire and supervised failure: 2, 350mA / nominal 19.5-28VDC (24 VDC) Fire and fault relays: 2 Auxiliary: 1, 500mA / 19.5-28VDC (24VDC nominal) |
Inputs | 2 x programmable supervised input in plate |
Serial port interface | 3 x RS232 |
USB interface | 3 x USB Type B for PC connection |
Program | Keyboard and LCD (built-in) |
Event Buffer | 9999 events |
Networks | Optional network card (ADV-MXP-503 - standard, or ADV-MXP-509 - fault tolerant) |
Main power supply | 110~240v 50/60 Hz AC (+10%, -15% tolerance) 3.15A Max |
Degree of protection | IP30 |
Type of mounting | Surface mounting |
Dimensions (W x H x D mm) | 450 x 581 x 169 mm |
Cable entry (20mm knockouts) | 18 at the top/ 2 at the bottom/ 2 removable plates at the back |
Battery capacity | 2x 12V 18Ah |