Primary power supply | Switching source 230V AC 50-60 Hz 2A max. |
Backup power supply | 2 batteries 12VDC (up to 7.2 Ah). Ensures minimum 120 hours duration. |
Number of zones | 4 zones, up to 32 detectors by area. (20 det. maximum of the range Dx700) |
Siren outputs | 4 Acoustic siren outputs 24VDC monitored max. 250mA |
Relay outputs | 1 Alarm output and 1 Fault output / 28VDC @ 2A max. |
Extra inputs | 2 |
End of line resistance | Areas fully monitored by end-of-line resistance (4.7K) |
Auxiliary Output Voltage | 24VDC and 250mA max. |
Protection Index | IP30 |
Temperature | -5ºC~+50ºC |
Material and colour | ABS, colour: White |
Dimensions | 435 x 320 x 129 mm |
Weight | 2.8Kg |
Recommended cable | Fire cable with a minimum section of 1.0mm (18AWG). |