TF-TFDA-TR1

Shipping in
48h
  • Thermal/Thermovelocimetric Detector
  • Thermal class A and B
  • Thermovelocimetric Suffix S or R
  • Line separator with double insulator
  • Mounting on universal base TFBASE01
  • Equipped with actuator for functional electrical test
  • Description
  • Specifications
  • Contents
  • Downloads

Addressable detector, thermal or thermovelocimetric sensing technology.

Maximum accuracy in determining the room temperature.

Programmable functions: Thermal category: A1-58° / A2-68° / B-78°, thermovelocimetric suffix: R or S, formula association and management actions for TFBASE-SIREN or TFRIP-SMART. The functional states of the detector can be used as operands in the formulas managed by the control panel.

CSR® Management: programming, remote management and control. Loop connection. Double line isolator.

Universal base mounting TFBASE01.

EN 54-5:2017 + A1:2018 - EN 54-17:2005. Certificate of homologation: 1293-CPR-0526 rv.1


  • TECNOFIRE
  • Analogical sensor addressable by rotary switch with thermal and/or thermovelocimetric sensing technology
  • Line separator (IN /OUT) with double isolator
Device name TFDA-TR1
Description Addressable thermal detector
Communication protocol FIRE-SPEED
Address 3 rotary selectors
Frequency of interrogation 2 levels
Communication WITNESS Signaling that can be excluded
Thermal Suffi R - S - None
Thermal class A1/A2 - B
Power From loop
Nominal voltage 24VDC
Operating voltage 18V...30VDC
Standby absorption 350μA @ 24V DC in absence of communication
Absorption in alarm 1,5mA @ 24V DC
Repeater output 9,4V DC 3mA (protected)
Line separator Intelligent isolator (no device loss)
Exercise temperature -15°C...+70°C
Relative humidity 10%...93% (in absence of condensation)
Protection class IP22
Container ABS V0
Dimensions (Ø x H) 100 x 52mm (including basis)
Weight 90g
Standards EN 54-5: 2000 + A1: 2002 - EN 54-17: 2005
Certificate of homologation 1293-CPR-0526
Year of CE marking 16
Benefit statement number 019_TFDA-TR1
Certification body EVPU
  • Analogical sensor addressable by rotary switch with thermal and/or thermovelocimetric sensing technology