TF-TFA1-298

Shipping in
48h
  • Analog fire panel of 1 loop
  • Capable of holding two batteries of 12V-7h.
  • The loop supports 199 sensors and 99 modules
  • User interface with color graphic display
  • Automatic report writing
  • Communication with CMS using TFCOM
  • Description
  • Specifications
  • Contenido
  • Downloads

Addressable fire detection control panel, equipped with 1 detection loop, the loop can control 199 detectors and 99 modules, and has 1 serial bus RS485 for connecting expansion devices, up to 5 a choice of repeater panels and/or telecommunication devices.

Manages 150 fire or technical detection zones and 100 virtual detection zones, 50 alert plans, 8 time slots, 100 formulas and customizable or perpetual four-year calendar.

Advanced management with logic determined by the application of formulas, dynamically relating the functional states of the system devices.

Equipped with 3 specialized signaling outputs and 2 freely programmable signaling outputs.

User interface: color display of 4,3”, programming and management keyboard, 16 LED signaling, voice synthesis and multifunctional acoustic signal speaker.

USB port, serial printer and RSC®: programming, remote management and control.

2,7A Modular Switching Power Supply. Battery compartment: 2 x 12V - 7.2Ah. Aluminum and steel cabinet.

Central office according to EN 54-2: 1997+ A1: 2006 - EN 54-4: 1997+ A1:2002 + A2:2006.

Type approval certificate 0051-CPR - 0444.

System compatibility IN 54-13:2020.


  • TECNOFIRE
  • Analog fire detection control panel with 1 loop with capacity of up to 298 addressable points
  • Fire-Speed Protocol
  • Three-color TFT graphic display 482X272 pixels
  • Communication with CMS IN 54.21
  • EN 54.2-4 certified
Total manageable detectors199
Total manageable modules 99 Total manageable modules99
Total manageable areas150
Virtual zones100
Specialized relays2
Open Collector programmable2
Controlled output for siren1
True Color TFT Display480 x 272 pixels
Vocal synthesisMultilingual dictionary
Detection loops1
BUS serial RS4851 - Master BUS
Event memory capacity4096
Access levels4
Access codes10
Supervised system modeProgrammable
Detection loopFire-speed
BUS RS485Fire-Bus
Formulas100
Alarm plans50
Time bands8
Calendar years4 (programmable)
Expansion devices BUS connection RS485 Maximum 5 unitsCentral repeater ,Synoptic repeater, Telephone combiner
Serial printerManagement
CPU Consumption200mA @ 24V d
Electrical OutputsMax. 50mA
Supply voltage Loop 20V...27,6VDC
BUS supply voltage RS485 20V...27,6VDC
Supply voltage sirens 20V...27,6VDC
Modular power supplyType A (switching)
Supply voltage230V AC +10 -15% 50Hz
Maximum absorbed current600mA ac
Nominal values2,7A @ 27,6V dc
Maximum supply currentI max. 2,7A
Ripple max≤230mV pp
Battery protectionT-1A Fuse
Flammability classV-2 or higher
Internal resistancemax. 1,5 Ω
Deactivation voltagePer Vbat <17,6V
Tiempo de recarga (2 x 12V/7Ah)100% en 24 horas
Clase medioambiental 3K5 EN 60721-3-3:1995
Temperatura de ejercicio+5° C... +40° C
Humedad relativava10%...93% (en ausencia de condensación)
Alojamiento batería2 x 12V/7,2Ah
Grado de protecciónIP30
ContenedorAluminio - Metal
Dimensiones (L x A x P)361 x 301 x 107mm
Peso (sin batería)2,7Kg
Certificación CentralEN 54-2: 1997+A1:2006
Certificación Fuente de alimentaciónEN 54-4: 1997+A2:2006
Certificación Número de certificación0051-CPR-0444
Certificación Año del marcado CE15
Certificación Número de la declaración de prestación015_TFA1-298
Organismo de certificaciónIMQ
  • Central de incendios analógica de 1 lazo