TOA-VX-3000DS

  • Power supply EN54 VX-3000
  • Main system power supply
  • Battery charger and UPS function
  • Supervised automatic switching
  • 8+3 DC outputs
  • Power 2300 W
https://d1x12lhh8s9nlj.cloudfront.net/images/productos/products/TOA-VX-3000DS/TOA-VX-3000DS
https://d1x12lhh8s9nlj.cloudfront.net/images/productos/products/TOA-VX-3000DS/TOA-VX-3000DS
  • Description
  • Specifications
  • Contents
  • Downloads
  • TOA
  • System emergency power supply VX-3000
  • Voice alarm EN54 and general public address system
  • Power supply of the system units
  • UPS backup in case of power failure
  • Battery charger
  • 8+3 DC outputs (Max. 25A/salida)
  • 2300 W
  • Automatic switching
  • Rack 19" 3U
ModelVX-3000DS
Power supply220 - 230 V AC, 50 / 60 Hz
OutputsDC output power:
8 x 31 V (19 - 33 V) 25 A max. each, screw terminal M4, distance between barriers: 11 mm
3 x 31 V (19 - 33 V) 5 A max. each one, removable terminal block (3 x 2 contacts)
1 x 24 V (16 - 25 V) 0,3 A max., removable terminal block (1 x 2 contacts)
Charging methodTemperature compensated dropping charge
Load output voltage27,3 V ±0,3 V (at 25 ˚C), Temperature correction coefficient: -40 mV/ ˚C
Battery connectionOne positive and one negative terminal, with applicable wire diameter: AWG 6 - AWG 0 (AWG 1/0) (16 mm2 - 50 mm2)
Line resistance within 4 mΩ / total
Monitoring connectorFemale RJ45 connector for connecting the system and cascading Straight shielded twisted-pair cable (standard TIA/EIA-568A)
DS LINK IN/OUTType of monitoring signal: Battery check, AC power supply status, DC power supply status, charging circuit failure, battery failure, and communication
Panel indicatorAC power supply IN 1, IN 2 (green), charging (green), battery power supply (green), battery connection (green), battery status (green)
Operating Humidity90 % RH or less (without condensation)
Operating temperature-5 °C up to +45 °C
FinishedSteel plate, surface treated, 30% brightness, painted, black
Dimensions482 x 132.6 x 400.5 mm (D x H x W)
Weight11,8 kg
Accessory (included)Fuse (T8A H) x 2, Fuse (T6.3A L) x 2, Blade fuse (35 A) x 2, Rack mounting screw (with washer) x 4, Power cable (2 m) x 2, Fixing hook x 4, Fixing loop x 4, Thermal insulation sheet x 1, Cable CAT5-STP (3 m) x 1, Ferrite clamp x 1
  • Power supply
  • Installation material
  • User instructions

alt