| Number of address loops | 2 |
| User selectable loop topologies | Class A (ring) or Class B (piece up to 32 devices) |
| 24 VDC outputs to field devices | 2 |
| Maximum number of devices | 400 |
| Maximum number of output groups | 400 |
| Maximum loop distance | 2.000 m |
| Recommended cable type | 2 x 1.5 mm² unshielded twisted pair |
| Maximum number of addressable points | 200 per Class A loop (max 2 x 200)) |
| Loop voltage | 20~30V |
| Available current per loop | 200 mA |
| External power outputs | 2 x 2A@24 VDC |
| Cable input | Perforations of Ø20 mm (14x) |
| Alarm and Fault Outputs | Normally open relays without voltage (up to 2A@30 VDC) |
| Power | 230 VAC (196 - 253 V) 2.5A max. |
| Protection fuse | 2.5 A |
| Max. dC output direct current (Imax a) | 5.5 A |
| Max. alarm DC output current (Imax b) | 4 A |
| Battery capacity | 2x 12V 7Ah~12Ah |
| Operating temperature | -5 to +40 °C |
| Storing temperature | -20 to +55 °C |
| Humidity (non condensing) | < 95 % |
| Degree of protection | IP30 |
| Dimensions | 440 (W) x 370 (H) x 126 (D) mm |
| Weight (without batteries) | 4 kg |
| Standards | EN 54-2 and EN 54-4 |
| DoP | DoP-0370-CPR-3813-1 |